Product Model
|
40C2H1000K
|
|
Battery string type
|
14S10P
|
|
Nominal capacity
|
2007kWh
|
|
AC connection
|
3-Phase 4-Wire+PE
|
|
Isolation
|
Built-in Transformer
|
|
Grid- connected voltage
|
400V
|
|
Dimensions (WDH)
|
11980x2438x2591mm
|

|
More Energy
|
All-in-one Design
|
Simple O&M
|
Safe & Reliable
|
|
Pack-level Optimization
String-level Optimization
|
AC/DC All-in-one Design
Reducing Initial Investment
|
No periodic balancing
No experts site visit
|
Modular Design
High Availability
|

|
BMU
|
|
CMU
|
|
||
|
Cell Voltage. Measurement Accuracy
|
±5mv
|
Battery String Voltage Measurement Range.
|
100~1,000V
|
||
|
Cell Voltage Monitoring Interval
|
≤200ms
|
Battery String Voltage Measurement Accuracy
|
±1%
|
||
|
Cell Temperature Measurement Accuracy
|
±2°C
|
Battery String Voltage Monitoring Interval
|
≤100ms
|
||
|
Cell Temperature
Measurement Interval |
≤3s
|
Battery String Current Measurement Range
|
±300A
|
||
|
Cell Current Balance
|
Passive Balance, 150mA MAX
|
Battery String Current Measurement Accuracy
|
≤1%
|
||
|
Cell Voltage Measurement Range
|
1~5V
|
Battery String Current Monitoring Interval
|
≤50ms
|
||
|
Over-current Protection
|
250A/1s
|
SOC Calculation Accuracy
|
≤8%
|
||
|
Short-Circuit Protection
|
500A/10ms
|
Input Insulation Resistance
|
≥10MO, 1000VDC
|
||